Home > Products
> Fiberglass Operating / Discharging Rod
|
|
 |
Fiberglass
Operating / Discharging Rod
|
 |
Application:
Earthing of High & Very high voltage lines
and sub-stations.
Material:
Fiber glass epoxy bonded class 'F' insulation, having
strong Electrical & Mechanical
Strength
-
Smooth glossy outer surface
- Available in 2, 3 or 4
Section.
-
Assembled height from 6
feet to 24 feet.
-
Screw type or Push button
type locking system
-
Type tested 650 KV CPRI,
Banglore
- Rotating type
adjustable line end clamp made out of Aluminum
alloy.
- Suitable
for Cylindrical Conductor from 5mm to 50mm dia & 4" dia
bus bar.
- Clamp provides
firm grip to conductor
- Metallic Earth
end clamp for earthing to be fix up with M.S. Structure.
-
Transparent insulated copper
cable with copper lugs from 10mm to 35mm.
|
|
Application:
Earthing of High & Very high voltage lines
and sub-stations.
For operation of D.O
Fuse from Ground Level.
66
to 132 Kv.
|
| Type |
Section |
Assemble
Height |
Withstanding
(DRY) |
| B-66 |
2 |
10
Feet |
15
kv/feet |
| B-66 |
3 |
15
Feet |
15
kv/feet |
| ES-132 |
3-4 |
18
Feet |
15
kv/feet |
132
to 220 Kv.
|
| ES-220-3-OR |
3 |
15
Feet |
40
kv/feet |
| ES-220-4-OR |
4 |
15
Feet |
40
kv/feet |
| ES-220-4-OR |
4 |
15
Feet |
40
kv/feet |
400
Kv.
|
| ES-400-5 |
4/5 |
14
Feet |
- |
| ES-400-5 |
4/5 |
16
Feet |
- |
| ES-400-5 |
4/5 |
18
Feet |
- |
| ES-400-5 |
4/5 |
20
Feet |
- |
|
|
The
introduction of FRP Telescopic Multipurpose Operating
Rods enjoyed
instant success in Electricity Boards and Industries.
The wide range acceptance is founded on it usefulness
in improving safety standards in Averting Fatal Accidents
During normal earthing operation as well as minimizing
shutdowns due to minor maintenance problem. Blazing
a trail of success, ARC has ventured into the
Hi-Tech During '95-'98 and after series of Research,
Developed Life Saving Equipments / Equipments to
improve efficiency.
For operation of D.O Fuse from Ground Level. |
|
|
|
TYPE
|
SECTION
|
ASSEMBLE
HEIGHT
|
WITHSTANDING
(DRY)
|
OR-11
|
3
|
15
Feet
|
12
kv/feet
|
OR-11
|
4
|
15
Feet
|
12
kv/feet
|
OR-11
|
4
|
18
Feet
|
12
kv/feet
|
Material
Tested: 33 KV Frp Discharge/operating Rod
in 4 Sectons
Test Specification: IS 2071 (Part 1) 1993 RA 1999
|
No.
|
Item
|
Result
Requd.
|
Result
Obtained
|
|
1
|
Lightning
impulse Voltage Withstand Test (between ends)
|
170
KV (Peak) |
Withstood |
|
2
|
Power
Frequency Voltage Withstand Test Dry (Between
ends)
|
100
KV (rms) |
Withstood |
|
3
|
power
Frequency Voltage Withstand Test Wet (Vetween
ends)
|
100
KV (rms) |
Withstood |
The
above material caters to the above specification. |
|